Fenwal Detect-A-Fire (D-A-F) detectors are rate-compensated thermal detectors that sense actual surrounding air temperature regardless of how fast a fire grows. They are used to signal overheat and fire conditions and to release suppression agents - clean agent, CO2, inert gas, wet chemical, dry chemical or water. The line covers 12 factory-set temperature points from 140 °F to 725 °F (60 °C to 385 °C) in vertical and horizontal configurations.
Control Fire Systems Ltd. is an authorized Kidde Fenwal Fire Systems distributor and First Fill Center in Toronto, Ontario, supplying, installing and servicing Detect-A-Fire detectors across Canada.
| Specification | Value |
|---|---|
| Detection principle | Rate-compensated fixed temperature (thermal) |
| Temperature settings |
Vertical: 12 settings, 140–725 °F (60–385 °C)
Horizontal: 7 settings, 140–325 °F (60–163 °C) |
| Vertical models | 27121-0, 27121-20, 27120-0, 27120-22, 28020-3, 28021-5 |
| Horizontal models | 27021-0, 27021-1, 27020-0, 27020-1 |
| Contact configuration | Single Pole Single Throw (SPST), normally open (close on rise) or normally closed (open on rise) |
| Electrical rating (resistive) | 5.0 A @ 125 VAC; 0.5 A @ 125 VDC; normally open models also 2.0 A @ 24 VDC and 1.0 A @ 48 VDC |
| Response Time Index (RTI) | 99–148 (ft-s)^1/2 — Quick, Fast or Very Fast depending on model and setting |
| Maximum rated spacing | Up to 30 x 30 ft (9 x 9 m) on smooth ceilings; 20 ft for clean agent and CO2 systems |
| Housing | Type 300 stainless steel sensing shell, cold-rolled steel mounting facility, off-white finish |
| Weight | Vertical approx. 5 oz; horizontal approx. 10 oz |
| Low-temperature exposure | Tested to -22 °F (-30 °C) per UL 521 |
| Approvals | UL listed, ULC listed, FM Approved, CE (IEC 60947-1 / 60947-5-1) |
| Service life | Test annually per NFPA guidelines; replace after 10 years of continuous service |
| Availability | Supplied from the Control Fire Systems facility at 63 Advance Rd., Unit A, Toronto. Current stock and lead time confirmed per model at quote. |
The detector shell is made of a rapidly expanding alloy that tracks the surrounding air temperature closely. The inner struts use a slower-expanding alloy and are sealed inside the shell so they resist thermal absorption. In a slow-growing fire the shell and struts heat together and the contacts operate at the factory set point. In a fast-growing fire the shell expands quickly, the struts close, and the detector reacts sooner - the faster the fire grows, the faster the response.
A transient rush of warm air of up to 40 °F per minute - for example from a process oven - expands the shell without triggering the detector, which is why Detect-A-Fire virtually eliminates the false alarms common to rate-of-rise devices.
| Device type | Under 10 °/min | 10–40 °/min | Over 40 °/min |
|---|---|---|---|
| Detect-A-Fire rate-compensated detector | 1st | 1st | 2nd - but at the selected protection level |
| Fixed-temperature detector | 2nd | 2nd | 3rd |
| Rate-of-rise detector | 3rd | 3rd | 1st - but may be a false alarm |
Vertical detectors are approved for both ordinary and hazardous locations. For ordinary use they mount to any approved junction box with a 7/8 in opening using 1/2-14 NPT mounting nuts, and may be wired in or out of conduit. Normally open vertical detectors are supplied with four lead wires so system wiring can be supervised. Mounted in an appropriately classified box they are UL and ULC listed and FM Approved for hazardous locations.
| Model | Head material | Contact operation | Electrical rating (resistive only) |
|---|---|---|---|
| 27120-0 | Brass | Normally closed (open on rise) | 5.0 A 125 VAC; 0.5 A 125 VDC |
| 27120-22 | Stainless steel | Normally closed (open on rise) | 5.0 A 125 VAC; 0.5 A 125 VDC |
| 27121-0 | Brass | Normally open (close on rise) | 5.0 A 125 VAC; 0.5 A 125 VDC; 2.0 A 24 VDC; 1.0 A 48 VDC |
| 27121-20 | Stainless steel | Normally open (close on rise) | 5.0 A 125 VAC; 0.5 A 125 VDC; 2.0 A 24 VDC; 1.0 A 48 VDC |
| 28020-3 | Stainless steel (coupling head) | Normally closed (open on rise) | 5.0 A 125 VAC; 0.5 A 125 VDC |
| 28021-5 | Stainless steel (coupling head) | Normally open (close on rise) | 5.0 A 125 VAC; 0.5 A 125 VDC; 2.0 A 24 VDC; 1.0 A 48 VDC |
| 12-200001-00X | Stainless steel | Normally open (close on rise) | Specialty product, limited availability — contact us |
Note: models 27120 and 28020 are normally closed two-wire devices. They do not meet the requirements of NFPA 72 for use as initiating devices and are not FM listed with an RTI. Approximate weight 5 oz; all shell material is Type 300 stainless steel.
| °F | °F tol. | °C | °C tol. | UL ft | ULC ft | FM ft | RTI | Colour |
|---|---|---|---|---|---|---|---|---|
| 140 | +7/-8 | 60 | +4/-5 | 50 | 50 | 20 | V-Fast | Black |
| 160 | +7/-8 | 71 | +4/-5 | 25 | 25 | 20 | V-Fast | Black |
| 190 | +7/-8 | 88 | +4/-5 | 50 | 50 | 25 | V-Fast | White |
| 210 | +7/-8 | 99 | +4/-5 | 25 | 50 | 25 | V-Fast | White |
| 225 | +7/-8 | 107 | +4/-5 | 25 | 50 | 25 | V-Fast | White |
| 275 | +/-10 | 135 | +/-6 | 25 | 50 | 25 | V-Fast | Blue |
| 325 | +/-10 | 163 | +/-6 | 50 | 50 | 25 | V-Fast | Red |
| 360 | +/-10 | 182 | +/-8 | 25 | 50 | 30 | V-Fast | Red |
| 450 | +/-15 | 232 | +/-10 | 25 | 50 | 30 | V-Fast | Green |
| 500 * | +/-15 | 260 | +/-10 | 50 | 50 | 30 | V-Fast | Orange |
| 600 * | +/-20 | 316 | +/-12 | N/A | 50 | 30 | V-Fast | Orange |
| 725 * | +/-20 | 385 | +/-12 | N/A | 50 | 30 | V-Fast | Orange |
* 500 °F, 600 °F and 725 °F settings are not available on normally closed detectors. For clean agent or CO2 suppression systems, ceiling spacing is 20 ft unless otherwise specified.
Horizontal detectors are designed for locations where appearance matters. The low-profile housing physically protects the detector and suits commercial, industrial, mercantile, institutional and marine applications in non-hazardous ("ordinary") locations. Flush-mount units fit standard 4 in octagonal electrical boxes; surface-mount units mount directly to ceilings or to 4 in junction boxes. Canadian Electrical Code requires mounting to an electrical junction box. Horizontal detectors use connector blocks instead of lead wires.
| Model | Mounting style | Contact operation | Electrical rating (resistive only) |
|---|---|---|---|
| 27020-0 | Flush mount | Normally closed (open on rise) | 5.0 A 125 VAC; 0.5 A 125 VDC |
| 27020-1 | Surface mount | Normally closed (open on rise) | 5.0 A 125 VAC; 0.5 A 125 VDC |
| 27021-0 | Flush mount | Normally open (close on rise) | 5.0 A 125 VAC; 0.5 A 125 VDC; 2.0 A 24 VDC; 1.0 A 48 VDC |
| 27021-1 | Surface mount | Normally open (close on rise) | 5.0 A 125 VAC; 0.5 A 125 VDC; 2.0 A 24 VDC; 1.0 A 48 VDC |
| °F | °F tol. | UL ft | ULC ft | FM ft | RTI | Colour |
|---|---|---|---|---|---|---|
| 140 | +7/-8 | 50 | 50 | 20 | Quick | Black |
| 160 | +7/-8 | 25 | 25 | 20 | Quick | Black |
| 190 | +7/-8 | 50 | 50 | 25 | Fast | White |
| 210 | +7/-8 | 25 | 50 | 25 | Fast | White |
| 225 | +7/-8 | 25 | 50 | 25 | Fast | White |
| 275 | +/-10 | 25 | 50 | 25 | Fast | Blue |
| 325 | +/-10 | 50 | 50 | 25 | Fast | Red |
Note: models 27020-0 and 27020-1 are normally closed two-wire devices; they do not meet NFPA 72 requirements for use as initiating devices and are not FM listed with an RTI. Approximate weight 10 oz.
Detect-A-Fire detectors are not position sensitive - "horizontal" and "vertical" describe the most common mounting configuration, and either type can be mounted in either orientation depending on the application.
| Model | Configuration | Set point | RTI | RTI class | RTI rated spacing |
|---|---|---|---|---|---|
| 27021-0 / 27021-1 | Horizontal, flush / surface, normally open | 140 °F (60 °C), 160 °F (71 °C) | 110 | Quick | 20 x 20 ft (6 x 6 m) |
| 27021-0 / 27021-1 | Horizontal, flush / surface, normally open | 190–325 °F (88–163 °C) | 140 | Fast | 25 x 25 ft (8 x 8 m) |
| 27121-0 / 27121-20 / 28021-5 | Vertical, brass / stainless / coupling head, normally open | 140–725 °F (60–385 °C) |
99 at 140–160 °F;
148 at 190 °F and above |
Very Fast | 30 x 30 ft (9 x 9 m) |
Spacings above are distances between detectors on smooth ceilings; distances from partitions or walls are half the figure shown. Always confirm the layout with the Authority Having Jurisdiction (AHJ) before installation.
| Ceiling height above | Up to and including | Derating factor |
|---|---|---|
| 0 m / 0 ft | 3.05 m / 10 ft | 1.00 |
| 3.05 m / 10 ft | 3.66 m / 12 ft | 0.91 |
| 3.66 m / 12 ft | 4.27 m / 14 ft | 0.84 |
| 4.27 m / 14 ft | 4.88 m / 16 ft | 0.77 |
| 4.88 m / 16 ft | 5.49 m / 18 ft | 0.71 |
| 5.49 m / 18 ft | 6.10 m / 20 ft | 0.64 |
| 6.10 m / 20 ft | 6.71 m / 22 ft | 0.58 |
| 6.71 m / 22 ft | 7.32 m / 24 ft | 0.52 |
| 7.32 m / 24 ft | 7.93 m / 26 ft | 0.46 |
| 7.93 m / 26 ft | 8.54 m / 28 ft | 0.40 |
| 8.54 m / 28 ft | 9.14 m / 30 ft | 0.34 |
| Model | Hazardous location | Fitting required for UL / ULC listing and FM approval |
|---|---|---|
| 27120-2, 27121-20, 28020-3, 28021-5 | Class I, Groups A, B, C and D; Class II, Groups E, F and G | Mount the detector to a suitable listed fitting in accordance with the National Electrical Code and/or the local authority having jurisdiction. |
| 27120-0, 27121-0 | Class I, Groups B, C and D; Class II, Groups E, F and G | Mount the detector to a suitable listed fitting in accordance with the National Electrical Code and/or the local authority having jurisdiction. |
An optional explosion-proof mounting box, P/N 06-116317-001, is available and complies with NEC Class I Groups A, B, C, D; Class II Groups E, F, G; Class III and UL Standard 1203. The explosion-proof mounting box is purchased separately from the detector.
| Agency | File number | Location |
|---|---|---|
| UL | S492 | Ordinary |
| UL | E19310 | Hazardous |
| ULC | CS341-E | Ordinary and hazardous |
| FM | J.I. OV2HO.AE | Hazardous |
| FM | 17302 | Ordinary |
| UL | S2410 | Ordinary (600 °F and 725 °F) |
| UL | E89599 | Hazardous (600 °F and 725 °F) |
| CE | IEC 60947-5-1 | — |
Detect-A-Fire detectors are UL and ULC listed and FM Approved both as fire detection thermostats (close on temperature rise) and as releasing devices (open on temperature rise). The product family has been evaluated to IEC 60947-1 and IEC 60947-5-1 and documented under Intertek Report No. 102294754 BOX-001 as an overheat detector, with rated insulation and impulse voltages of 1500 VAC.
Ordering example: 27121-20 at 190 °F with fluorocarbon coating.
Not sure which set point your hazard needs? Send us the maximum ambient temperature and ceiling height and we will specify the model, setting and spacing.
Model 27121-0 (vertical, brass head, normally open) is a stocked detector in all twelve temperature settings from 140 °F to 725 °F. Other models and settings are stocked in limited quantities or manufactured on demand.
| Model | Configuration | Settings available | Supply | Action |
|---|---|---|---|---|
| 27121-0 | Vertical, brass head, normally open | 12 settings, 140–725 °F | Toronto facility — stock confirmed at quote | Request price |
| 27121-20 | Vertical, stainless, normally open | 12 settings, 140–725 °F | Toronto facility — stock confirmed at quote | Request price |
| 27021-1 | Horizontal, surface, normally open | 7 settings, 140–325 °F | Toronto facility — stock confirmed at quote | Request price |
| 28021-5 | Vertical, coupling head, normally open | 12 settings, 140–725 °F | Toronto facility — stock confirmed at quote | Request price |
The “Settings available" column is taken from the Fenwal F-12-0-001 datasheet, so the table is publishable as it stands. Per-model stock counts and firm lead times are the only fields the warehouse still needs to fill in.
As an authorized Kidde Fenwal distributor and First Fill Center we also supply the matching release panels, cylinders and agent - see Fenwal 732 release panels.
The Fenwal Series 17343 monitors for fire and overheat conditions in very high temperature environments. It is recommended as an alarm device that alerts supervisory staff so corrective measures can be initiated. Like the Detect-A-Fire line it provides rate compensation, activating at a predetermined danger point whether heat builds slowly or quickly.
We install and service these systems for industrial facilities, power generation, data centres and server rooms, automotive facilities and commercial kitchens across Canada.
Control Fire Systems performs code-compliant fire alarm device testing, inspection and suppression system service in Ontario, from Toronto, Mississauga and Ottawa. Equipment supply, cylinder refilling, hydrostatic testing and Halon recycling are available Canada-wide.
“I purchased a fire alarm from you and it helped us detect a kitchen fire last week." — Jerry Manzo
“Professional, fast and neat. They did all my fire system work for my commercial building. On-time. They have great technicians." — Sina Jam
“They came in time for our fire alarm and suppression system installation last week and provided fast and efficient service." — T. Friesen
Technical data from Fenwal Controls datasheet F-12-0-001, Rev. BC. Page last reviewed September 2026 by the Control Fire Systems technical services team.